CalculationsSidewall Pressure
Cable Installation

Sidewall Pressure

Check bend pressure against the cable manufacturer limit.

Engineering basisConduit bend pressureSingle and three-cable arrangementsManufacturer limits
FORMULAS USED
Single cable / common jacket
SP = T/R
Three single-core cables, cradled
SP = (3*w-2)*T/(3*R)
Three single-core cables, triangular
SP = w*T/(2*R)
Radius required by pressure limit
R_required = pressure*R/limit

T: total tension leaving the bend, N. R: effective bend radius, m. w: weight correction factor. SP: sidewall pressure, N/m.

N
m
N/m
Use the documented limit for this cable. Leave blank to calculate pressure without a limit check.
mm
mm
Reset

Engineering References

Southwire Power Cable Installation Guide

E-20 to E-22: single/common-jacket, three cradled, three triangular. Geometry and weight factors: Figure F-13 and E-16 to E-18.

Source
Project cable manufacturer limit

Enter the documented limit for the actual cable. No universal pressure limit is preselected. This pressure check does not establish pulling-tension, fill, jamming or bending-radius compliance.

Source