UL 1685 FT4 / IEEE 1202 / UL 2556 Section 9.6 Method 2 (CSA method)

Started by Kalliope Taciarchai, February 28, 2015, 01:01:22 PM

Previous topic - Next topic

Kalliope Taciarchai



UL 1685 FT4 / IEEE 1202 / UL 2556 Section 9.6 Method 2 (CSA method)

Test set-up The cables are secured to a ladder in a single layer (quantity depends on the diameter of the cable). The length of each sample is 2.44 m. Cables with a diameter of <13 mm are secured to the ladder in bundles. The burner is tilted at an angle of 20°.

Flame temperature

Determined by the stipulated quantity of propane gas and air. The power equals 20.5 kW (70,000 Btu/hr).

Test duration 20 minutes (2 tests to be performed)

Compliance criterion

The area of fire damage to the cables must be less than 1.5 m (measured from the bottom edge of the burner nozzle).