• Welcome to CableDataSheet, Cable and Wire Technical Consulting Service.
 

News:

You are not allowed to view links. Register or Login
You are not allowed to view links. Register or Login
You are not allowed to view links. Register or Login
You are not allowed to view links. Register or Login



Main Menu

IEEE 1580 Cable Code Designation

Started by cabledatasheet, June 26, 2013, 01:27:36 PM

Previous topic - Next topic

cabledatasheet



IEEE 1580 Cable Code Designation

(informative)
Previously used cable designations

The following information is for historical purposes only. This has been replaced with 5.19 marking
requirements.

D.5.19 Previously used cable designations

D.5.19.1.1 Cable type (service symbol)

"S"           Single conductor distribution
"D"           Two conductor distribution
"T"           Three conductor distribution
"F"           Four conductor distribution
"Q"           Five conductor distribution
"C"           Control cable (1)
"TP"         Twisted pair (1)
"TT"         Twisted triad (1)
(1) = Insert AWG size of conductors following service symbol for C, TP, and TT.
D.5.19.1.2 Shielding

No marking     Unshielded
"OS"                Overall shield
"IS"                 Individual shield
"IS-OS"           Individual and overall shield
"OBS"             Overall braid shield

D.5.19.1.3 Insulation type (2)

"E"           Ethylene propylene rubber
"X"           Crosslinked polyethylene
"P"           Crosslinked polyolefin
"S"           Silicone rubber
"LSX"      Low smoke, halogen-free crosslinked polyolefin
"LSE"      Low smoke, halogen-free ethylene propylene rubber
"LSS"       Low smoke, halogen-free silicone rubber
"T"           Polyvinyl chloride
"T/N"       Polyvinyl chloride/nylon
(2) = For insulation types E, X, T, T/N, and S where the VW-1 is the option, the letter "V" is
added after the insulation type to indicate compliance with this optional requirement.

D.5.19.1.4 Jacket type

"T"           Polyvinyl chloride
"CP"         Chlorosulfonated polyethylene
"N"           Polychloroprene (neoprene)
"L"           Low smoke, zero halogen crosslinked polyolefin
"TPO"      Low smoke, zero halogen thermoplastic polyolefin
"CPE"      Thermoset chlorinated polyethylene

D.5.19.1.5 Armor

No marking         Unarmored
"A"                     Aluminum armor
"B"                      Bronze armor
"T"                      Tinned copper armor
"_S"                    Armor and sheath (3)
"CWCMC"         Continuously corrugated metal armor

(3) = Add the type of armor, A, B, or T, before the S.


D.5.19.1.6 Size
The wire size is designated for distribution cable by adding a dash (-), followed by the conductor
size in kcmil.


D.5.19.1.7 Voltage rating


The rated distribution cable voltage is added to the symbol following a dash (-), as follows:
2 000 V                          2 kV
5 000 V                          5 kV
8 000 V                          8 kV
15 000 V                        15 kV
25 000 V                        25 kV
28 000 V                        28 kV
35 000 V                        35 kV

The complete type designation should include the following parts:
—    Cable type (S, D, T, F, Q, C, TP, TT)
—    Shielding designation, if applicable
—    Insulation type
—    Jacket type
—    Armor, if applicable
—    "S" if jacket over armor

For Types S, D, T, F, and Q, distribution cables.
Following a dash (-), the conductor size in kcmil is as follows:

—    DTTB-4  =  AWG  14  (4.11  kcmil),  two-conductor,  polyvinylchloride-insulated, 
thermoplastic
polyvinyl chloride jacketed, and bronze armored
—    SXNA-250  =  250  kcmil,  single  conductor,  cross-linked  polyethylene  insulated, 
Thermoset neoprene jacketed, and aluminum armor
—    TPNBS-313 = 3 conductor, 313 kcmil, polyolefin insulation with neoprene jacket, bronze armor,
and overall sheath

Following a second dash (-), the voltage rating is as follows:
—    TPNBS-313-5KV = 3 conductors, 313 kcmil, polyolefin insulation with neoprene jacket, bronze
armor, and overall sheath, 5 kV.

For Types C, TP, and TT, the number of conductors, pairs or triads, as applicable; the number  of
conductors of control, and the number of conductor pairs/triads of signal cable, is added to the
cable designation, as follows:
—    C14TCPB-20  =  20  conductor  control  cable,  14  AWG,  thermoplastic-insulated,  Thermoset
chlorosulfonated polyethylene jacketed, and bronze armor
—    TP18TNA-10  =  10  twisted  pair  signal  cable,  18  AWG,  thermoplastic-insulated, 
Thermoset neoprene jacketed, and aluminum armor
—    C14PCP-3  =  3  conductor,  14  AWG,  polyolefin  insulated,  and  chlorosulfonated 
polyethylene jacketed
—    TP (OS) 18PNBS-2 = 2 twisted pairs, 18 AWG with polyolefin insulation, overall tape shield and
drain wire, neoprene jacketed, with bronze armor and overall outer sheath


Document echo ' ';