HD620 10-A Cable Code Designation

Table 5 – Type Designations

Cables according to this section are designated by:

1. Abbreviated code description of the cable by using the following symbols:
SymbolDescription
E-Cable according to this section
XSpecial cable which is not specified in this standard
AAluminium conductor
-Copper conductor (no symbol)
2XXLPE-insulation
HSemi-conducting layer
CCopper screen
CECopper screen, individual
YPVC-Sheath
2YPE-Sheath
J2YLongitudinal water tightness with PE sheath
JA2YLongitudinal and transversal water tightness with Al/PE sheath
JC2YLongitudinal and transversal water tightness with Cu/PE sheath

2. Number of cores times (x) nominal cross-sectional area of conductor in mm²

3. Indications of form and type of conductor as given hereafter:
SymbolDescription
RCircular conductor
SSector shaped conductor
MStranded conductor
ESolid conductor

4. After a stroke (/):
Nominal cross-sectional area of screen

5. Rated voltage Uo/U in kV
Document echo ' ';