IEC 60332-1-2 / EN 50265-2-1 / VG 95218-2 Method 1 / BS 4066 Part 1

Test set-up The single cable to be tested is fixed vertically and exposed to a Bunsen burner flame at a 45° angle to the vertical.

Flame temperature
Determined by the specified setting of the Bunsen burner flame.

Test duration
Cable with a diameter of ≤ 25 mm: 60 sec
Cable with a diameter of 25 < D < 50 mm: 120 sec

Compliance criterion
The fire damage must end at least 50 m below the upper fixing clamp. The cable must be self-extinguishing.