CableDataSheet, Cable and Wire Technical Consulting Service

Technical Paper => General Cable Information => Topic started by: Kalliope Taciarchai on February 28, 2015, 01:33:57 PM

Title: BS 6387 Category Z
Post by: Kalliope Taciarchai on February 28, 2015, 01:33:57 PM
(https://ir9dxq.dm1.livefilestore.com/y2p3hIvWk8h7Ek28YuC0eCdG9EA-1APzcFg7UWhCRdHo-TpFEkCx504u_d6i_rJ9Z5U-AQDcKP-D4xnJCWOYmGlGaer2bkd2SQy6bdWuJcoxUs/books.png?psid=1)

BS 6387 Category Z

Test set-up The cable is fixed on a positioning board and flame is applied from below. The positioning board is subjected to 2 knocks every minute during the burn period.

Flame temperature

950 °C ± 40 °C

Test duration 15 minutes

Compliance criterion

It must be possible to transmit power or signals through all conductors while the flame is applied. There must be no short circuit between the conductors or to the shield.

https://onedrive.live.com/view.aspx?cid=A212A7DB96D6B5B0&resid=A212A7DB96D6B5B0!1829&app=WordPdf