• Welcome to CableDataSheet, Cable and Wire Technical Consulting Service.
 

News:

You are not allowed to view links. Register or Login
You are not allowed to view links. Register or Login
You are not allowed to view links. Register or Login
You are not allowed to view links. Register or Login
Tacettin İKİZ



Main Menu

What is the cable voltage drop and formulation?

Started by tacettin, September 03, 2024, 11:59:47 AM

Previous topic - Next topic

tacettin

You are not allowed to view links. Register or Login

tacettin

If the cable meets European standards, the formula is as follows:

European Formula (mV/A/m)

VD = R x I x L / 1000
VD: The voltage drop (V).
R: The resistance value from voltage drop per ampere per meter table (mV/A/m)
supplied by the cable manufacturer.
I : The load current (A)
L: The length of conductor (m)
The value R is determined from a table provided by the cable manufacturer. See Table 1
below as an example of a table that is provided by a manufacturer.
Below is an example calculation for determining voltage drop.
Determine the voltage drop of a 380V, 3 phase circuit with a current of 100A and a
length of 150 m and a conductor size of 35 mm. This is a secondary service feed.
The voltage drop of secondary service is limited to 3% (380 x 3% = 11.4 Volts).
Volt drop = Resistance x Current x Length / 1000. Resistance is found on Table 1
below.
VD = 1.1 x 100 x 150 / 1000
= 16.5 V

The maximum voltage drop allowed is 11.4 V. To determine the size of cable that will be
required to meet the voltage drop requirement, determine the value of R that will meet the
requirement.
11.4 = R x 100 x 150 / 1000
R = 11.4 x 1000/100 x 150
= 0.76 mV/A/m
Referencing the table provided by the cable manufacturer (Table 1), the cable that has a
resistance of .76mV/A/m or less is a 70 mm cable with a resistance of 0.55 mV/A/m.
Calculating the voltage drop for the 70mm cable results in:
VD = R x I x L / 1000
= 0.55 x 100 x 150 / 1000
= 8.25 V
The percentage voltage drop is:
Percentage Voltage Drop = 8.25 x 100 / 380 = 2.17 %
Therefore, in order to transmit a 3 phase current of 100A per phase over a length of 150
m, with a total voltage drop equal to or less than the maximum 11.4 volts, a 70 mm cable
is needed.
This same procedure would be repeated for a feeder or branch circuit and the results
added. The total voltage drop should not exceed 5%


source :
You are not allowed to view links. Register or Login

Document echo ' ';