Scenario:- Cable Type: 3-core, 3x95 mm² copper cable (XLPE insulation, PVC sheath)
- Installation: Underground, in duct (typical for long-distance industrial applications)
- Length: 300 meters (one-way)
- Load: 3-phase, 400 A
- Voltage: 400 V
- Power factor (pf): 0.9
- System: 3-phase AC, 50 Hz
Step 1: Ampacity CheckLet's assume the ampacity of a 3x95 mm² Cu XLPE cable underground is about:
Ampacity ≈ 330 A (based on 30°C ambient temp and standard installation)
⇒ Result: Your load is 400 A, but the cable's ampacity is only 330 A.
This means 3x95 mm² is not sufficient for current carrying capacity.
You would need a larger size such as 3x150 mm² (typically rated around 445–470 A underground).
Step 2: Voltage Drop CalculationVoltage drop in a 3-phase system:
ΔV = √3 × I × (R × cosφ + X × sinφ) × L
Where:
- ΔV = voltage drop (V)
- I = 400 A
- R = 0.195 Ω/km = 0.000195 Ω/m
- X = 0.080 Ω/km = 0.000080 Ω/m
- L = 300 m
- cosφ = 0.9
- sinφ = √(1 - 0.9²) ≈ 0.436
ΔV = √3 × 400 × [ (0.000195 × 0.9) + (0.000080 × 0.436) ] × 300
ΔV ≈ 1.732 × 400 × (0.0001755 + 0.0000349) × 300
ΔV ≈ 1.732 × 400 × 0.0002104 × 300
ΔV ≈ 43.74 V
Percentage voltage drop:
%ΔV = (43.74 / 400) × 100 ≈ 10.94%
⇒ Result: This is above the recommended 3% limit.
Therefore, 3x95 mm² fails the voltage drop requirement as well.
Conclusion:The 3x95 mm² cable:
- Fails ampacity requirement (330 A < 400 A)
- Fails voltage drop requirement (10.94% > 3%)
Recommendation:- Use
3x150 mm² or
3x185 mm² cable (recheck values for confirmation)
- Or use
parallel cables such as 2x(3x95 mm²) if larger cross-sections are not practical