Cable Short-circuit capability


All cables should be checked to ensure they are capable of carrying the available fault current. The shortcircuit rating of an insulated conductor is based on the maximum allowable conductor temperature and insulation temperature. Conductor temperature is dependent on the current magnitude and duration. Equation (C.14) is used to estimate conductor temperature and is valid only for short durations. The maximum recommended conductor temperature is 250 °C to prevent conductor annealing.





source: IEEE Std 525-2007

Tacettin İKİZ

Cable Short-Circuit Capability

All cables should be checked to ensure they are capable of carrying the available fault current. The short-circuit rating of an insulated conductor is based on the maximum allowable conductor temperature and insulation temperature. Conductor temperature is dependent on the current magnitude and duration.

Equation (C.14) is used to estimate conductor temperature and is valid only for short durations. The maximum recommended conductor temperature is 250 °C to prevent conductor annealing.

QuoteSource: IEEE Std 525-2007



Key Considerations for Cable Short-Circuit Capability:
  • Fault Current Capacity: The cable must be rated to handle the peak fault current it may encounter.
  • Maximum Conductor Temperature: Typically limited to 250°C to prevent annealing of the conductor.
  • Insulation Temperature Limits: Insulation materials have specific temperature ratings that should not be exceeded.
  • Duration of the Fault: Shorter fault durations result in lower temperature rises.
  • Material Properties: Copper and aluminum conductors have different thermal characteristics affecting their short-circuit ratings.


Standard Calculation for Conductor Temperature Rise:

The conductor temperature during a short circuit is estimated using the Adiabatic Heating Equation:

T_f = T_i + (I² * t) / (k² * A²)

Where:
  • T_f = Final conductor temperature (°C)
  • T_i = Initial conductor temperature (°C)
  • I = Short-circuit current (A)
  • t = Fault duration (seconds)
  • A = Conductor cross-sectional area (mm²)
  • k = Material constant (dependent on conductor type and insulation)


Material Constants (k-values) from IEEE Std 525-2007:


MaterialInsulation Typek (A·s½/mm²)
CopperPVC115
CopperXLPE143
CopperEPR130
AluminumPVC76
AluminumXLPE95



Design Considerations:
  • The calculated T_f should not exceed 250°C.
  • Ensure the cable insulation can withstand the temperature rise.
  • Proper cable sizing is required based on fault current magnitude and duration.